MCB C60N7 years text(1)

 

Icons-4-web-big

 

MCB C60N data sheets

 

Technical characteristics:
– Rated operating voltage: 230/400V; 50/60Hz
– Rated current: 1-63А
– Breaking capacity: 6000 А
– Poles: 1; 2; 3;4
– Tripping curve: B;C
B- the maximum current release breaks between 3 and 5 In; used to protect long circuits and generators

С – the maximum current release breaks between 5 and 10 In; used to protect main power supply cables and conventional consumers

– Electrical wear resistance (number of cycles):≥8000
– Mechanical wear resistance (number of cycles):≥50000
– Limitation class: 3
– IP code: IP>20
– Ambient temperature: -5 to +40°С±2°С

 

Mounting: Vertically on a DIN rail

 

Standard: EN60898-1

 

More pictures